Time:2021-09-29

Please leave a message for us and we will reply in the first time

SUNDI -10℃~200℃
Heating Power:2.5kW~15kW
Dimension(cm):45*65*120~120*110*195
Weight:115kg~300kg
Support OEM customization!

PRODUCTS

  • sundi-2.jpg

    Dynamic Temperature Control System Advantages And Functions: 

    Temperature range from -120℃~350℃, superior performance, high precision, intelligent temperature control. Multi-function alarm system and safety function, 7-inch, 10-inch color TFT touch screen graphic display, magnetic drive pump, no shaft seal leakage problem.

    sundi外观结构.jpg


    SUNDI YUANLI.png

    Structural design principles & Functional advantages:

    No heat transfer medium evaporates at high temperature, and continuous control of -80~190℃, -70~220℃, -88~170℃, -55~250℃, -30~300℃ can be realized without pressurization. temperature;


    The fully enclosed pipeline design reduces the demand for thermal fluid while increasing the heat utilization rate of the system to achieve rapid temperature rise and fall. The heat-conducting medium in the expansion vessel does not participate in the circulation, which can reduce the risk of the heat-conducting medium absorbing moisture and volatilizing during operation.

    lr-2.jpg

    Simultaneously control the temperature of the reactor jacket and the material;

    Exclusively designed lag predictor (no model self-built tree algorithm) + general anti-lag cascade algorithm;

    Three-point temperature sampling (material temperature point, equipment outlet temperature, equipment inlet temperature);

    The self-developed high-performance circulating pump has low noise and is more suitable for rapid endothermic and exothermic reactions.


    Model

    SUNDI-125/125W

    SUNDI-135/135W

    SUNDI-155/155W

    SUNDI-175/175W

    SUNDI-1A10/1A10W

    SUNDI-1A15/1A15W

    Temp. range-10℃~+200℃
    Control ModeFeedback PID + Our special dynamic control calculation, PLC controller
    Temp. controlProcess temp. control and jacket temp. control model
    Temp. differenceSet or control the temperature difference between jacket oil and raw material process
    Program Editor10 programs, each program can edit 40 steps
    Communication PortocolMODBUS RTU Protocol, RS485 interface
    Material temp. feedbackPT100 OR 4~20mA or communication(normal: PT100)
    Temp. feedbackThe temp. of three points: the inlet and outlet of equipment,reactor material temp.(external temp. sensor)
    Medium temp. acccuracy±0.5℃
    Material temp. accuracy±1℃
    Heating power kW2.5~15
    Cooling capacity kW at200℃2.5~15
    20℃2.5~15
    -5℃1.5~9
    Circulation pump maxL/min bar20~75
    2~2.5
    CompressorMitsubishiMitsubishiEmerson copeland vortex flexible
    Expansion valveEmerson thermal expansion valve/danfoss thermal expansion valve
    EvaporatorDANFOSS/KAORI Plate heat exchanger
    Operation Panel7-inch touch screen,show temp curveEXCEL data output
    Safety protectionSelf-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device, liquid low level protection, high temperature protection and temperature fault protection.
    Closed circulation systemThe whole system is full closed circulation, there is no oil mist at high temperature and no water vapor at low temperature, pressure do not rise up when system is running. The system will supply oil automatically at low temperature.
    RefrigerantR404A/R507C, optional: R448A